User manual

Bulletin 836E
Condition Sensing
6-36
Visit our website: www.ab.com/catalogs
Rockwell Automation
SENSORS
Product Selection
Solid-State Pressure Switches
Dual PNP Output or 4…20 mA Analog with Single PNP Output
Media temperature range from -40…100°C (-40…212°F)
Operating temperatures from -40…85°C (-40…185°F)
Industry-leading four-digit 14-segment digital display
Independently programmable dual PNP N.O./N.C.
outputs or 4…20 mA analog outputs
Accuracy is <0.5% of upper pressure range limit
Repeatability is <0.2% of upper pressure range limit
IP66 enclosure rating
316L stainless steel; fluorinated elastomer seals
Dual PNP Output
Process
Connection
Pressure Range
(psig)
Set Point Range
(psig)
Reset Point Range
(psig)
Maximum
Working
Pressure
(psig)
Cat. No.
1/4 inch NPT
(female)
-15…15 -14.92…+15 -15.00…14.92 40.5
836E-DA1CC1D4
0…60 0.30…60 0…59.70 160.5
836E-DA1EL1D4
0…150 0.75…150 0…149.25 400.5
836E-DA1EN1D4
0…600 3.00…600 0…597.00 1600.5
836E-DA1EQ1D4
0…1,500 7.50…1,500 0…1,492.50 1600.5
836E-DA1ER1D4
0…400 (bar) 2.07…413.79 (bar) 0…400 (bar) 400 (bar)
836E-DA1EU1D4
SAE 7/16-20
UNF (female)
-15…15 -14.92…+15 -15.00…14.92 40.5
836E-DA1CC2D4
0…60 0.30…60 0…59.70 160.5
836E-DA1EL2D4
0…150 0.75…150 0…149.25 400.5
836E-DA1EN2D4
0…600 3.00…600 0…597.00 1600.5
836E-DA1EQ2D4
0…1,500 7.50…1,500 0…1,492.50 1600.5
836E-DA1ER2D4
-15…15 -14.92…+15 -15.00…14.92 40.5
836E-DA1EU2D4
G1/4 BSPP
(female)
-1…1 (bar) -1.0…+1.03 (bar) -1.03…1 (bar) 2.7 (bar)
836E-DA1CC3D4
0…4 (bar) 0.02…4.14 (bar) 0…4 (bar) 10.7 (bar)
836E-DA1EL3D4
0…10 (bar) 0.05…10.30 (bar) 0…10 (bar) 26.7 (bar)
836E-DA1EN3D4
0…40 (bar) 0.21…41.38 (bar) 0…40 (bar)
106.7
(bar)
836E-DA1EQ3D4
0…100 (bar) 0.52…103.45 (bar) 0…100 (bar)
106.7
(bar)
836E-DA1ER3D4
-15…15 -14.92…+15 -15.00…14.92 40.5
836E-DA1EU3D4
Recommended Cordset: 2 m (6.5 ft) 4-pin DC Micro QD / M12 (straight)
889D-F4AC-2
Recommended Cordset: 2 m (6.5 ft) 4-pin DC Micro QD / M12 (right angle)
889D-R4AC-2
Maximum working pressure (MWP) is the maximum pressure a switch can tolerate for an indefinite period of time.
Over pressure limit is the maximum pressure a switch can tolerate for a short period of time without sustaining
permanent damage. Burst pressure limit is the maximum pressure a switch can tolerate without sustaining
permanent damage or leakage.
Other cable lengths are available. Shielded cables may be required for some analog output applications. Refer to
the On-Maschine Connectivity catalog for additional information.