User manual

Bulletin 440L
Presence Sensing
5-15
Visit our website: www.ab.com/catalogs
Rockwell Automation
Features
Type 4 models correspond to EN61496
PNP outputs (2 N.O safety + 1 N.O aux.)
Range: 0.4…16 m
Beam coding
External device monitoring (EDM)
Start/restart interlock
Protected Height (mm) Response Time Number of Beams Restart Cat. No.
520 mm
20 ms, 30 ms with beam
coding activated
2 Automatic
440L-P4A2500YD
820 mm
20 ms, 30 ms with beam
coding activated
3 Automatic
440L-P4A3400YD
GuardShield 3-beam PAC - Type 4, 400 mm Resolution
SAFETY
Product Selection
Cordsets - Two Required (one for transmitter and one for receiver)
Female Connector (Sensor End) Cable
Wire Rating Length [m (ft)]
Cat. No.Face View of Female
Connector
Style
Pin/Wire
Color
Transmitter
4
3
1
2
Straight
Female
1 Brown
2 White
3 Blue
4 Black
22 AWG
300V
4 A
2 (6.56)
889D-F4AC-2
5 (16.4)
889D-F4AC-5
10 (32.8)
889D-F4AC-10
15 (49.2)
889D-F4AC-15
20 (65.6)
889D-F4AC-20
30 (98.4)
889D-F4AC-30
Receiver
5
6
7
8
4
3
1
2
Straight
Female
1 White
2 Brown
3 Green
4 Yellow
5 Grey
6 Pink
7 Blue
8 Red
24 AWG
30V AC/36V
DC
1.5 A
2 (6.56)
889D-F8AB-2
5 (16.4)
889D-F8AB-5
10 (32.8)
889D-F8AB-10
15 (49.2)
889D-F8AB-15
20 (65.6)
889D-F8AB-20
30 (98.4)
889D-F8AB-30
440L GuardShield Safety Light Curtains, PAC (Perimeter Access Control)
See publication S117-CA001… for complete product information.