User manual
Bulletin 140UE
Molded Case Circuit Breakers
1-18
Visit our website: www.ab.com/catalogs
Rockwell Automation
POWER
Frame Reference H-Frame J-Frame L-Frame M-Frame N-Frame
Current Range 20…160 A 70…250 A 100…630 A 300…800 A 600…1250 A
No. of Poles 3, 4 3, 4 3, 4 3 3, 4
Dimensions
(mm)
Height 140 178 258 406 406
Width 76 105 140 210 210
Depth 76 103 104 140 140
Interrupting Ratings: kA
I
cu
I
cs
I
cu
I
cs
I
cu
I
cs
I
cu
I
cs
I
cu
I
cs
50 Hz
220…240V
25, 35,
85, 100
50%
65, 85,
100
100%
65, 85,
100
100% 65, 100 100% 200, 200 100%
380…415V
18, 25,
40, 70
50%
23, 40,
70
100%
35, 50,
70
100% 50, 70 100% 70, 100 100%
690V 6, 6, 7, 8 50% 6, 6, 7, 8 50% 2, 20, 25 50% 20, 25 100% 35, 50 50%
60 Hz NEMA On request
Protection Type
Thermal-Magnetic FF, AF AA AA AF —
Electronic —
Internal Accessories
Alarm (Trip) Contact
Auxiliary Shields
Aux/Alarm
Combination
Shunt Trip
Undervoltage Release
Field Installable
External Accessories
Padlockable Hasp
Terminal Covers
Flex-Cable Operating
Mech.
Variable Depth Rotary
Operating Mechanism
Direct Coupler Rotary
Operating Mechanism
—
Plug-in Base
——
Slide Bar Interlock
Standards Compliance
IEC 60947-2
CE
KEMA-KEUR
Product Selection See page 1-19 See page 1-20 See page 1-21 See page 1-22 See page 1-22
Molded Case Circuit Breakers 140UE
Product Line Overview