POWER
Cat. No. 140M-H Cat. No. 140M-J Cat. No. 140M-L
Short Circuit Protection — Magnetic Trip (Adjustable at 3...10 x I
e
)
Overload Protection — None (Magnetic Trip Only)
Product Selection
Motor Circuit Protectors (MCP)
Rated Operational
Current (I
e
)
Magnetic Trip
Current
Switching of 3-Phase AC Motors
AC-2, AC-3 @ 400/415V (50 Hz)
Cat. No.[A] [A] [kW]
I
cu
[kA]
H-Frame
3 9…33 0.75 (65)
140M-H8P-B30
7 21…77 2.2 (65)
140M-H8P-B70
15 45…165 5.5 (65)
140M-H8P-C15
30 90…330 11 (65)
140M-H8P-C30
50 150…550 22 (65)
140M-H8P-C50
70 210…770 30 (65)
140M-H8P-C70
100 300…1100 45 (65)
140M-H8P-D10
100 500…1500 55 (65)
140M-H8R-D10
J-Frame
100 500…1000 37 (65)
140M-J8P-D10
125 625…1250 45 (65)
140M-J8P-D12
150 750…1500 55 (65)
140M-J8P-D15
175 875…1750 55 (65)
140M-J8P-D17
200 1000…2000 75 (65)
140M-J8P-D20
225 1125…2250 90 (65)
140M-J8P-D22
250 1250…2500 90 (65)
140M-J8P-D25
L-Frame
225 1125…2250 90 (65)
140M-L8P-D22
250 1250…2500 90 (65)
140M-L8P-D25
300 1500…3000 110 (65)
140M-L8P-D30
350 1750…3500 132 (65)
140M-L8P-D35
400 2000…4000 160 (65)
140M-L8P-D40
450 2250…4500 160 (65)
140M-L8P-D45
500 2500…5000 200 (65)
140M-L8P-D50
600 3000…6000 250 (65)
140M-L8P-D60
N-Frame
800 1600…6400 250 (65)
140M-N8P-D80
1200 2400…9600 400 (65)
140M-N8P-E12
Tested @ 480V 60 Hz according UL 489