User manual
Product Line Overview
Device Selection
Bulletin 4983-DH 4983-DS 4983-DD 4983-DC
Type
DIN Rail Heavy-Duty
AC Surge Protective
Device
DIN Rail Standard
Duty AC Surge
Protective Device
DIN Rail Dataline
Surge Protective
Device
DIN Rail
Combination Filter
and Surge
Protective Device
Features
High energy
absorption
capability
Visual fault
indicator linked to
internal thermal
disconnect
Automatic trigger
for SPD
replacement
Remote signaling
Compact modular
design
Visual fault
indicator linked to
internal thermal
disconnect
Automatic trigger
for SPD
replacement
Remote signaling
Compact modular
design
Protects industrial
communication
networks
Small combination
(filter and SPD)
package size
Features Islatrol
®
technology
LED power
indication
AC Network
110…120V AC (1
wire)
220…230V AC (1
wire)
380…400V AC (1
wire)
120V AC 1-phase
120/208V AC 3-
phase + N
480Y/277V AC 3-
phase + N
230V AC 1-phase
230/240V AC 3-
phase + N
110…120V AC (1
wire)
220…230V AC (1
wire)
380…400V AC (1
wire)
120V AC 1-phase
120/208V AC 3-
phase + N
480Y/277V AC 3-
phase + N
230V AC 1-phase
230/240V AC 3-
phase + N
4…20 mA loop,
RS232 type, High
speed transmission
(LAN), RS485 type,
RS422 type
—
Operating Voltage — 120 or 240V AC
Max. Continuous
Operating Voltage
150V AC
330V AC
150…400V AC 8…28V DC
150 Vrms (125%) @
120V AC
320 Vrms (115%) @
240V AC
Ampacity — 3…20 A
Line Frequency — 47…63 Hz
Protection Level 1 or 1.5 kV 0.7…2 kV 25…40V —
UL1449 Suppressed
Voltage Rating (SVR)
0.4 or 0.6 kV 1.5, 1.9, or 1.5 kV — —
Standards
Compliance/
Certifications
UL 1449, CSA C22.2
No. 8, IEC 61643-1,
CE, EN 61643-11
UL 1449, CSA C22.2
No. 8, IEC 61643-1,
CE, EN 61643-1
UL 497B, IEC 61643-
1, CE, EN61643-11
UL 1283, UL 1449,
CE
Operating
Temperature (non-
condensing)
-40...+85 °C
-40...+60 °C derate
linearly to 60% @
+70 °C
Product Selection Page 2-48 Page 2-49 Page 2-50 Page 2-50
LOGIC
Rockwell Automation
Visit our website: www.ab.com/catalogs
2-47
Bulletin 4983
Filter and Surge Protective Device