Product Line Overview
Device Selection
LOGIC
Rockwell Automation
Visit our website: www.ab.com/catalogs
2-35
Bulletin 1489 1492-FB
Type
480Y/277V AC 240V AC
For Class
CC Fuse
For Class J Fuse
For Midget
Fuse
0.5…25 A 0.5…40 A 30 A 30 A 60 A 30 A
Features
True IP2X finger-safe design
(front)
10,000 A interrupt
A postively trip-free
mechanism (breaker operation
cannot be defeated by holding
the handle in the ON position)
Superior shock and vibration
resistance capabilties
Mounts on DIN Rail
IEC 60947-2
- 0.5...40 A @ 240, 415V AC
- 15,000 A interrupting
Field-mountable options
Optional terminal for ring lugs
EN/IEC 60529 Front Finger Protection — Dead
front construction
Handle isolates the fuse from line power when it
is opened for fuse insertion or removal
Compact size requireing less panel space than
open style fuse folders
Optional blown fuse indicators - allow for easy
troubleshooting of electrical circuits
Type M holder - accepts 0…30 A midget fuses (1
1/2" x 13/32")
Type C holder - accepts 0…30 A Class CC fuses)
Type J 30 & 60 A holders - accepts Class J fuses
Silver-plated fuse clips
Mounts on DIN rail, marker-ready and increased
heat dissipation
Certifications
UL 489 Listed (CSA C22.2 No.
5.1), UL File Number E197878
VDE (SEC 60 947-2)
CE, ULus, CSA CE, URus, CSA
Maximum Voltage Rating 480Y/277V AC 600V AC/DC
Shock
25 G Half Sine Wave for 11 ms
(Three Axes)
25 G Half Sine Wave for 11 ms (Three Axes)
Tripping Characteristic
Reference Temperature
40°C (UL/CSA)
30°C (IEC)
NA
Tripping Characteristic
C Curve: 5…10
D Curve: 10…20
NA
Vibration
100...500 Hz for 1 hour
Amplitude — 10...57 Hz; 0.030
inches peak to peak; 57...500
Hz; 5 G peak
5 G peak or 0.030 "peak-to-peak" displacement for
2 hours in each perpendicular direction. Vibration
sweep 10 to 2000 to 10 Hz (15 minutes long)
Operating Temperature
-13...140°F (-25...+55°C),
non-condensing
-4...130°F (–20…+55°C)
Housing Material Nylon Nylon
Working
Voltage
—
110…600V
AC/DC or
12…72V
AC/DC
110…600V AC/DC
110…600V
AC/DC or
12…72V
AC/DC
With
Indicator
Leakage
Current
LED
— 2.0 mA
Wire Size 0.8...13 mm
2
/#18...6 AWG Cu
#16…4 AWG
Cu
#14…1
AWG Cu
#10…1
AWG Cu
#16…4 AWG
Cu
Interrupt Rating
10 kA @ 240V AC and
480Y/277V AC (UL/CSA)
200 kA 50 kA
Product Selection See page 2-43 See page 2-45
Bulletin 1492-RCD, 1492-SP, 1492-FB, 1489, 140F
Circuit Protection