User`s manual
10 - 3 10 - 3
MELSEC
10 ERROR CODE
Return value
(HEX)
Error definition Corrective action
Special module time over
No response from the specified special module.
Check the hardware of the special module.
242
(F2
H)
No response from the MELSECNET (II) board.
Check the hardware of the MELSECNET (II)
board.
1280
(500
H)
Host board memory access error
Check the switch setting on the host board and
move the memory address to the area that is not
effected by other board.
Change the memory access setting to 16 bit if it is
set to 8 bit.
1281
(501
H)
Unable to access I/O port
Check the I/O port address setting.
Perform a board self-loopback test and check the
hardware.
4110
(100E
H)
DLL non-load error
8204
(200C
H)
Request cancel
8205
(200D
H)
Drive name error
8206
(200E
H)
First step error
8207
(200F
H)
Parameter type error
8208
(2010
H)
File name error
8209
(2011
H)
Registering/release/set status error
8210
(2012
H)
Detailed condition division error
8211
(2013
H)
Step condition error
8212
(2014
H)
Bit device condition error
8213
(2015
H)
Parameter setting error
8215
(2017
H)
Keyword error
8216
(2018
H)
Read/write flag error
8217
(2019
H)
Refresh method error
8218
(201A
H)
Buffer access method error
8219
(201B
H)
Start mode/stop mode error
8220
(201C
H)
Written clock data error
8221
(201D
H)
Online data write error
8223
(201F
H)
Trace time error
8224
(2020
H)
First I/O number error
8225
(2021
H)
First address error
8226
(2022
H)
Pattern error
8227
(2023
H)
SFC block number error
8228
(2024
H)
SFC step number error
8229
(2025
H)
Step number error
Exit the program and restart the PC.