User`s manual
9 - 6 9 - 6
MELSEC
9 MELSEC DATA LINK LIBRARY
9.6 Station Number Settings
The following lists the station numbers specified via functions.
Communication Station number specification
CC-Link
Host: 255 (0xFF)
Other station:
1
,
2
1 :
Network No.
0: When CC-Link is used
Higher Lower
Station No. or group No.
1(1h) to 64(40h), other station
<How to specify the logical station number>
Set "0" to the upper byte (network No.) of the station number
described above, then specify the logical station number to
the lower byte (station number).
The range of the logical station number specification is from
65(41
H
) to 239(EF
H
).
2 : It is impossible to specify the station number 64 on the CC-Link communication
except for the buffer memory access.