User`s manual

5 - 6 5 - 6
MELSEC
5 PROCEDURE AND SETTINGS UP TO THE POINT OF OPERATION
A80BDE-J61BT13
DB
DG
SLD
FG
NC
NC
NC
NC
NC
DG
DA
DB
SLD
DA
DG
24GDA +24V
DB
SLD
FG
DB
DG
SLD
FG
NC
NC
DA
QJ61BT11
Master module
CC-Link dedicated cable
Module other
than QJ61BT11
Terminal
resistor
Remote module
Ground the SLD terminal of
A80BD-J61BT13 as needed
Terminal
resistor
[Simplified Diagram] The following shows a simplified diagram of the connection
diagram on the previous page.
DA
DB
DG
SLD
FG
A80BDE-J61BT13
DA
DB
DG
SLD
DA
DB
DG
SLD
FG
Master module
Terminal
resistor
CC-Link
dedicated cable
Remote module
Ground the SLD terminal
of A80BDE-J61BT13
as needed
Terminal
resistor
CC-Link
dedicated cable
POINT
(1) The layouts of the terminal block for the QJ61BT11 and of the terminal blocks
for other than the QJ61BT11 are different. Exercise caution when wiring them.
(2) Be sure to connect a “terminal resistor,” which is provided with the master
module, to the modules at both ends of the data link. (Connect it between DA
and DB.)