User`s manual
2 - 4 2 - 4
MELSEC
2 EMC COMMAND
(2) Grounding treatment for the CC-Link dedicated cable
(a) Always ground the twisted cable connected to the CC-Link master station,
local station and remote station.
Since the twisted cable is a shielded cable, remove part of the outer sheath.
Then ground the exposed part of the shield indicated in the figure below as
wide a surface area as possible.
CC-Link dedicated cable
Shield
Control panel
All of this area should be grounded.
Always use the cable specified for
this cable.
Remote station Remote stationLocal station
Control panel
Also, ground within 30 cm (11.81.in.) from the board terminal area in addition
to grounding at the position closest to the exit of the control panel.
(b) Always use the specified cable for the CC-Link dedicated cable.
(c) For each module, do not use a ferrite core for the CC-Link dedicated cable
from the board.
(d) For each module, ground both the FG terminal and SLD terminal of the
board.
DA
DB
DG
SLD
FG
DA
DB
DG
SLD
24V
24G
FG
DA
DB
DG
SLD
24V
24G
FG
Terminal
resistor
Terminal
resistor
Master module Remote module Local module
CC-Link dedicated cable