User`s manual
11 - 7 11 - 7
MELSEC
11 TROUBLESHOOTING
11.4 Flowchart to Use when the Data Link could not be Completed
The following flowchart indicates when the data link could not be completed even
though the CC-Link board was connected to another station.
YES
NO
YES
NO
YES
NO
START
Complete
Check the A80BDE-J61BT13 LED.
Is the "RUN" LED unlit?
See Section 11.4.1,
"Flowchart to use when RUN LED
is unlit."
Is the "SD/RD" LED lit?
See Section 11.4.2,
"Flowchart to use when the SD/RD LED
does not light."
Start the monitor function (utility) and
select line monitor from the menu.
Is an error occurring?
See Section 11.4.3.
"Flowchart to use when there is a
communication error in the master
station and CC-Link boards."