Technical data

Fieldbus coupler/controller • 55
Fieldbus coupler 750-310
WAGO-I/O-SYSTEM 750
CC-Link
3.1.4.4.17 Incremental Encoder Interface Module
750-631, 750-634, 750-637
Link register Signal name
high
byte
low
byte
Link register Signal name
high
byte
low
byte
RWrn(k) Statusbyte 0 S RWwn(k) Controlbyte 0 C
RWrn(k+1) Databytes 0 / 1 D1 D0 RWwn(k+1) Databytes 0 / 1 D1 D0
RWrn(k+2) Databytes 2 / 3 D3 D2 RWwn(k+2) Databytes 2 / 3 D3 D2
3.1.4.4.18 Digital Impuls Interface Module
750-635
Link register Signal name
high
byte
low
byte
Link register Signal name
high
byte
low
byte
RWrn(k) Statusbyte /
Databyte 0
D0 S RWwn(k) Controlbyte /
Databyte 0
D0 C
RWrn(k+1) Databytes 1 / 2 D2 D1 RWwn(k+1) Databytes 1 / 2 D2 D1
3.1.4.4.19 Serial Interface Module
750-650, 750-651, 750-653, 750-654
Link register Signal name
high
byte
low
byte
Link register Signal name
high
byte
low
byte
RWrn(k) Statusbyte /
Databyte 0
D0 S RWwn(k) Controlbyte /
Databyte 0
D0 C
RWrn(k+1) Databytes 1 / 2 D2 D1 RWwn(k+1) Databytes 1 / 2 D2 D1
RWrn(k+2)
*)
Databytes 3 / 4 D4 D3 RWwn(k+2)
*)
Databytes 3 / 4 D4 D3
*) RWrn(k+2) and RWwn(k+2) are only used if 6 bytes are mapped.