Technical data
Fieldbus coupler/controller • 43
Fieldbus coupler 750-310
WAGO-I/O-SYSTEM 750
CC-Link
3.1.2.7 Baud Rate and Address Mode
The CC-Link-coupler supports five different Baud rates (156 Kbps, 625 Kbps,
2,5 Mbps, 5 Mbps and 10 Mbps) and two address modes (fixed address mode
and auto address mode).
In auto address mode the coupler determines the number of adresses according
to the plugged modules (one to four addresses per station).
In fixed address mode the coupler determines the number of adresses fixed to
four addresses irrespective to the plugged modules.
A selector switch is used to set Baud rate and address mode.
Fig. 3-7:Baud rate and address mode selector switch g013903x
Address-Area
Fixed address mode
Address-Area
Auto address mode
Baud rate
Position of the selector switch
156 Kbps
05
625 Kbps
16
2.5 Mbps
27
5 Mbps
38
10 Mbps
49
The configuration is only read during the power up sequence. Changing the
switch position during operation does not change the configuration of the
buscoupler. Turn off and on the power supply for the fieldbus coupler to ac-
cept the changing.