Instruction manual

Voltage Tap Selection
CC/CCS Power Conditioner User Manual 23
moving the winding jumper lead(s) on the
primary side of the transformer.
Refer to the transformer schematic in Fig.
6 for the CC2333, CC2338, CC2350, and
CC2357.
Refer to the transformer schematic in Fig.
7 and terminal drawing in Fig. 8 for CCS
Series Products.
NOTE: To operate at 208 Volts input and 208
Volts output use the same tap selection as 240
Volts input and 240 Volts output.
5. Torque all connections as per Maintenance
on page 19.
6. Re-install the cover panel.
7. Mark any nominal voltage changes on or
near the rating nameplate.
8. Follow the procedure in Section 2.2,
Verifying Your Installation.
Fig. 6: CC Power Conditioner Transformer
Schematic
NOTE: The centered tapped secondary coil
output of these CC series power conditioners
can be wired from the factory as either
grounded 240 V (terminal 5 ground referenced)
or 240/120 split phase (terminal 6 ground
Transformer Schematic for Models
CC2333, CC2338, CC2350 and