Voltage Tap Selection
CC/CCS Power Conditioner User Manual 21
Fuse Replacement Output fuses are located above the conditioner's
receptacles or hardwire terminal connections.
The fuses protect the ONEAC power
conditioner from overload.
WARNING : Turn off the input and main output
circuit breakers on the power conditioner. Turn
off the power source supplying the power
conditioner at the service disconnect before
proceeding.
WARNUNG: Die Eingangs- und
Hauptausgangs-
Leistungsschutzschalter am
Leistungsanpassungsgerät abschalten. Vor dem
nächsten Arbeitsschritt muß die
Stromversorgung zum
Leistungsanpassungsgerät am
Wartungstrennschalter abgeschaltet werden.
1. If a fuse blows, replace the blown fuse with
the same rating and type.
Fuse type: Midget (5AG).
Use a time delay fuse such as:
Bussmann FNW Series or Littelfuse
FLM Series
NOTE: Some models do not have fuses.
2. Follow the procedure in Verifying Your
Installation on page 4, as required.
Voltage Tap
Selection
Tap selection allows a permanent adjustment to
the voltage level. If the nominal output level is
not within the equipment manufacturers
suggested operating range, you can move the
power tap on the primary of the power
conditioners transformer as an adjustment.
NOTE: Tap selection should be completed by a
qualified electrician, only.
The purpose of tap selection is to configure the
input of the power conditioner to accept the
desired voltage or to correct for steady state