Instruction manual

Installation and Operation
10 CC/CCS Power Conditioner User Manual
recommends that power runs on the output
of the conditioner be as short as possible,
with a maximum length of 50 feet (15 m).
4. Use wire sizes as recommended by the
National Electrical Code for lengths up to
25 feet (7.6m). For lengths from 30 feet
(9.1m) up to 50 feet (15.2m) increase the
NEC recommendations, for 60ºC
insulation, by 2 wire sizes (i.e. 10 gauge
rather than 12 gauge).
5. Torque all connections. Refer to the torque
specifications in
Maintenance on page 19.
6. Make sure there is an equipment grounding
conductor connected between the
receptacle on the ONEAC power
conditioner output and your equipment.
7. Turn OFF the ONEAC power conditioner
circuit breaker and your equipment.
8. Plug your equipment into the appropriate
receptacle on the ONEAC power
conditioner. The power conditioner should
be as close as possible to your equipment.
9. Turn ON the ONEAC power conditioner
and then your equipment.
10. Begin normal operation of your
equipment.
Hardwire output connected models
1. Follow the procedure for connecting the
input connections, see
Input Connections
on page 6.
2. Follow the U.S. National Electrical Code
and your local codes.
WARNING : Turn off the main power source
supplying the power conditioner at the service
disconnect before proceeding.
WARNUNG : Vor dem nächsten Arbeitsschritt
muß die Hauptnetzversorgung zum
Leistungsanpassungsgerät am
Wartungstrennschalter abgeschaltet werden.