Install Instructions

Installation
Mounting
It is recomme nded to mount the plate heat exchanger o n the
oor, on feet or on the wall.
Larger heat exchangers should be s ecured with s upport
mountings (ordered as accessory) intended for a specic heat
exchanger, or be sec
ured with straps or by m eans of mounting
bolts.
Note!
Regardless of the m o
unting method m inimize the
pipe loads at installation.
Maximum tightening torques for the mounting bolts according
to table below.
Bolt dimension Torque
Nm
lbf*ft
M5 2.3 1.7
M6 3.8 2.8
M8 9.5 7.0
M8 (Extra small units) 8.0 5.9
M10 19.0 14.0
M12 33.0 24.3
UNC 1/4”
3.8 2.8
UNC 5/16” 8.6 6.4
UNC 3/8”
15.6 11.5
In a rigid pipe system, small heat exchangers can be
suspended directly in the pipework. To avoid vibrations, us e
anti-vibration mounting according to picture be low.
Document ID
Language
Edition
3450021401 EN 2017-06
Instruction M anual -
Brazed plate heat exchangers
15
EN