Installation
Connection loads at installation
Fs
Ft
Mt
Mb
Figure 3. Connection loads.
Withreferencetodefinitions in figure, the loads during
installation s hould not exceed the limits specified in table below.
Maximum recomm ended c
onnection loads during
installation
D
Figure 4. O uter diam
eter of the connection (D).
Tension
force
Bending
moment
Shear
force
1
Torque
Outer diameter
mm (inch)
F
t
kN (lbf)
M
b
Nm
(lbf*ft)
F
s
kN (lbf)
M
t
Nm
(lbf*ft)
15 -28
(0.6 - 1.1”)
2.4
(539)
14
(10.3)
0.7
(157)
38
(28.0)
29 - 35
(1.1 - 1.4”)
4.0
(899)
45
(33.2)
1.2
(269)
120
(88.5)
36 - 45
(1.4 - 1.8”)
6.5
(1461)
110
(81.1)
2.5
(562)
240
(177.0)
46 - 55
(1.8 - 2.2
”)
7.0
(1573)
120
(88.5)
4.8
(1079)
440
(324.5)
56 - 76
(2.2 - 3.0”)
12.0
(2697)
250
(184.4)
5.2
(1169)
600
(442.5)
77 - 99
(3.0 - 3.9”)
13.0
(2922)
310
(228.6)
5.8
(1303)
1200
(885.0)
100 -
(3.9” - )
28.0
(6294)
800
(590)
5.8
(1303)
2500
(1843)
1. Shear force (Fs) is calculated assuming that the force is
applied at the end of the longest standard connection.