Installation Instructions
IntelliGaze™ Installation & Service Manual IntelliGaze™ Reference
6.6 Service Mode
The Service Mode allows the adjustment of internal system parameters by the experienced system
integrator.. It can be invoked by starting “IntelliGaze-Service” from the Program Menu.
The Service-Mode is not meant to be used by the end-user!
SERVICE-Mode - The program link should be deleted before delivery.
It can easily be recreated: the Service Mode is internally linked to starting intelligaze.exe with a
command-line parameter 'service' - i.e. RUN: “intelligaze.exe service”
Eye Tracking
Parameter
Parameter Default
Value
Description
Hardware Data Source Camera Choose whether you want to operate the system in mouse
simulation mode or in standard camera mode
Speed 40Hz Recommendation:
50Hz for real time applications like games (CAM30 only)
30Hz for computers at the lower end of the hardware
recommendation
Power Saving 1 for the Tablet PCs to optimize battery lifetime.
Standby-Time 15s The device will power down to an energy saving mode when
there is no head in the working range for the given amount of
time
Eye-Display -on- When turned on, you can activate an eye display in IntelliGaze™.
The eye display might help to solve problems that occur when
dealing with glasses
Log Log-Level Warning Chooses the debug level of the application. When set to verbose,
the system will write all internals into the logger; when set to
error, only error message will be logged.
© alea technologies gmbh, 2015
Version: 3.0
69