Installation manual
4.1.1.2 ENVIRONMENT
4.1.1.2.1 Climatic conditions
- Operation
• Temperature: for maximum reliability, it is recommended you comply with an ambient
temperature of between 5 and 40 degrees Celsius, with a maximum variation of 5
degrees Celsius per hour.
• Humidity: the humidity must be in the range 10% - 80% (no condensation) with a
maximum variation of 10% per hour.
- Storage
• Temperature: the temperature must be kept between -20 and +70 degrees Celsius.
• Humidity: the humidity must be kept in the range 10 - 95% (no condensation).
4.1.1.2.2 Vibration
No vibration, even intermittent, may be transmitted to the equipment when running.
4.1.1.2.3 Site
- Choose a dry, clean and well ventilated location.
- Maintain an ambient air flow to ensure normal ventilation. If the air flow is blocked or
restricted, of the incoming air is too hot, overheating is possible.
- When installing he equipment in an enclosed 19" rack, verify that the rack is provided with
a fan suited to the heat dissipation of the equipment installed. Maintain a minimum gap of 3
cm around the side ventilation holes (left and right sides), and of 10 cm minimum around
the ventilation holes at the rear of the equipment. Verify that the air flow is not impeded on
the sides of the rack.
- When fixing the system directly to the wall using the wall-mounting kit (Rack1 and Rack2
only), maintain a free space of at least 15 cm around the whole system. Ensure that no
objects are placed on the upper part of the system to restrict the extraction of hot air. When
installing several units, it is preferable to align then horizontally. When superposing them
vertically, they should be separated by at least 10 cm.
- Verify that the cables connecting the Alcatel-Lucent OmniPCX Office Communication
Server or other equipment, or the supports for the housing structure (19" rack for example)
do not obstruct the air flow through the unit.
- A switchable 230 V or 110 V mains socket (according to country) - 50Hz (LNE) is required
at less than 1 m from the unit unless it is installed in a rack in which case the integrated
circuit breaker is used.
- Adequate lighting must be provided.
4.2 Connections and Cabling
4.2.1 Detailed description
4.2.1.1 OUTPUT CONNECTORS
*+
4-3