User Guide
OmniAccess SafeGuard Controller Installation Guide
23
Chapter 2: Site Preparation and Installation
We recommend that you provide a 10-A fuse on your external DC connection to
safeguard against connecting the power source with the incorrect polarity.
The SafeGuard Controller does not have a power switch. To be able to disconnect the
power cords when needed, make sure that the power connections are easily accessible.
Make sure that the AC power input source connection is within 8 feet of the SafeGuard
Controller installation location.
Rack Requirements
The SafeGuard Controller is designed to fit into an industry-standard, 19-inch four-post
or two-post (telco-style) equipment rack. The rack should meet the requirements listed in
Ta ble 6 .
Environmental Requirements
To ensure optimal system operation, make sure that the installation site meets the
environmental requirements listed in Tab le 7.
Table 6 Rack Requirements
Rack type EIA standard 19-inch, four-post or two-post
Vertical rack space needed 1 RU—1.7 inches (4.4 cm) for each installed SafeGuard
Controller
Horizontal depth needed 18.6 inches (47.2 cm)
Stability Bolted to the floor, ceiling, wall, or other secured racks
Grounding Grounded
Strength Support for 20.0 pounds (9.1 kg) for each installed Safe-
Guard Controller
Table 7 Environmental Requirements
Operating temperature 0° C to +40° C
Storage temperature 0° C to +40° C
Operating relative humidity 5 to 90% (non-condensing)
Storage relative humidity 5 to 95% (non-condensing)