Instruction manual

2. Preparation for Installation
45
2.4 Power supply facility
2.4.1 Power supply facility for 100 V AC
(1) Outlet
Use an outlet shown below, that conforms to the JIS and NEMA standards. This
type of electrical outlet is available from electrical equipment suppliers.
Table 2-2 Electrical outlet standards
Standards Specifications
JIS C-8303
NEMA 5-15R
15A 125V, two-pin grounded outlet
Figure 2-4 Two-pin grounded outlet (125V 15A)
When using the Switch at 100 V AC, always use a grounded power
outlet. Using the Switch without grounding could result in electric
shock or failures due to electrical noise.
(2) Distribution board
Use circuit breakers on the branch circuit supplying power to the Switch. See the
following table for the rated breaker capacity, and the required number of circuit
breakers and outlets.
Table 2-3 Rated breaker capacity and required quantity
Rated breaker
capacity
Power supply
redundancy
Number of required
circuit breakers
Number of required
outlets
None 4 4
15 AT with single
phase 100 V AC (for
a 15 A circuit)
Required 8 8
NOTE
For easy operation, the distribution board should be installed in the
same room as the Switch or in an adjacent room.
NOTE
For a redundant power supply, the power from different power supply
systems can be supplied to each power supply unit.
(3) Requirements for the incoming current to the distribution board
The capacity of the incoming current to the distribution board must be greater than
that of the breaker operating current described in the above
(2) Distribution board.