Instruction manual

2. Preparation for Installation
42
2.2 Installation conditions
The general installation requirements for the Switch are described below. The
installation environment must meet these requirements.
Table 2-1 Switch installation conditions
Specifications Item
When an AC power supply
unit is installed
When a DC power supply unit
is installed
Dimensions (Width
#1
x Depth
#2
x
Height)
443 x 544 x 395 mm 443 x 573 x 395 mm
Weight (with maximum number
installed)
82 kg
Rated breaker
capacity
Single phase 100 to 120 V AC
Single phase 200 to 240 V AC
48 V DC
Input
voltage
#3
Variation range 90 to 132 V AC
180 to 264 V AC
40.5 to -57V
Frequency
50/60 ± 3Hz
--
Maximum input current 40A @ 100 V AC,
20A @ 200 V AC
79A @ 48 V DC
Maximum power consumption 3,750 W
Maximum heat dissipation 13,500k J/h
Intake temperature
25
o
C
60 dB or less
Noise
#4
Intake temperature
40
o
C
65 dB or less
Vibration 2.45 m/s
2
or less
Dust
#5
0.15 mg/m
3
or less
Operating 0 to 40
o
C (23 to 28
o
C is recommended)
Not operating 10 to 43
o
C
Temperature
During storage
and transportation
25 to 65
o
C
Operating 10 to 85% (45 to 55 % is recommended)
Not operating 8 to 85 %
Humidity
#6
During storage
and transportation
5 to 85 %
#1: Dimensions of the rack fixture are not included.
#2: Dimensions for the handles of the Switch, fan unit, and power supply unit are
included.
#3: The power cable supplied with the Switch supports only 100 V AC.
#4: The value is measured at 1 m from the side of the Switch. The number of
rotations of the fan varies according to the intake temperature. Because of this, the
value of the noise changes.
#5: According to JIS Z 8813 Measuring Methods for Suspended Particulate Matter
Concentration in Air.
#6: No condensation