2. Preparation for Installation
80
(3) Conditions for the Incoming Power to the Distribution Board
The capacity of electrical current supplied to the distribution board needs to be larger than that of the breaker operating
current shown in (2) Distribution Board.
(4) Providing Two Power Supply Systems to the Electrical Power Equipment
To build a redundant power supply system, provide another system of electrical power equipment to serve.
2.3.2 Electrical Power Equipment for 200 V AC
(1) AC Power Supply Cable
Use the power supply cable described below.
Table 2-10 Specifications of AC Power Supply Cable
(2) Electrical Outlet
Use the electrical outlet described below. These electrical outlets are available at general electrical contractors.
Two-pole grounded twist-locking receptacle (10 A/250 V)
Ensure that the capacity of incoming current to the distribution board should be
larger than the breaker operating current capacity. Otherwise, the breakers cannot
operate properly in case of trouble, which may cause a fire.
Generally, the breaker operating current is larger than the rated current. Check the
specifications of the circuit breaker.
Item
Connector
on the device
Cable
Plug
for the outlet
Rating 10 A, 250 V
Japan PSE certified
10 A, 250 V
Japan PSE certified
10 A, 250 V
Japan PSE certified
Shape Triplex Prepare a plug that suitable for
the outlet.
Make sure to connect the AC power model to a grounded outlet. Not connecting the
grounded outlet to the device can cause electric shocks, as well as cause a failure
due to electrical noise.