Instruction manual
2. Preparation for Installation
36
2.3 Electrical power equipment
2.3.1 Electrical power equipment for 100 V AC
(1) Standards for electrical outlets
Use the electrical outlets conforming to the following JIS or NEMA standard. These
electrical outlets are available at general electrical contractors.
Table 2-5 Standards for electrical outlets
Standards Specifications
JIS C-8303 15 A/125 V, 2-pole grounded straight-blade
receptacle
NEMA 5-15R
Figure 2-2 Two-pole grounded outlet (15 A/125 V)
Always use a grounded power outlet for the Switch. Failure to do so might not only
result in electric shock, but it might also introduce unwanted electrical noise that
could cause a Switch failure.
(2) Distribution board
The branch circuit to supply power to the Switch requires circuit breakers or other devices.
When selecting circuit breakers, make sure that they meet the following rating, considering
the input current and inrush current/time.
Rated breaking capacity: 15AT (for a 15 A circuit) or less
For details about input current of the Switch, see
2.2.1 General installation conditions, and
for details about inrush current and time of the Switch, see
Table 2-6 Inrush current.
Table 2-6 Inrush current
Series Model
Current (peak
value)
Time
AX2200S AX2230S-24T 15A 10 ms or less
AX2230S-24P 15A
AX1200S AX1250S-24T2C 30A
AX1240S-24T2C 15A