1.0 INSTRUMENT OVERVIEW
1.1 FEATURES
2 Point automatic calibration
Galvanically isolated probe inputs
2 Point automatic calibration
RF Technology
Arjay pulse card system for simple, safe, remote control, calibration and maintenance
Up to 4 Differential Alarm relays (SPDT 10A contacts) field mappable to either probe
Isolated mA output per probe Independently selectable as Direct / Inverse & 4-20 / 0-20mA
output with offset capability
RS-485 Modbus protocol
No moving parts
For use with any Arjay Capacitance probe
1.2 DESCRIPTION
The unit senses level using a RF capacitance measurement technique for very high-resolution
measurements. A probe mounted in a vessel forms a capacitor with the vessel wall, or with a
concentric shield around the probe for non-metallic vessels (ground reference). The capacitance of
this arrangement is directly proportional to the level of material in the tank and may be measured to
provide signals and controls.
Probe inputs and mA outputs are all galvanically isolated to minimize electrical interference.
The Arjay Level-Ease 2000 Series system uses RF (radio Frequency) methodology to measure the
vessel capacitance. This technique minimizes the effects of other electrical properties of the probe,
vessel, and vessel contents and focuses only on the vessel capacitance. The controller may be
located up to one km away from an Arjay probe via inexpensive 2 wire shielded cable.
Model 2100 series controllers offer a 20 character by 4 line LCD and 16 key membrane keypad offer
detailed data displays plus ease of calibration and setup. Level is displayed in percentage fill and in
user selectable engineering units. In addition a bar graph gives a quick indication of level.
Model 2300 series controllers are “blind” and have no display or keypad.
Figure 1.0
BLOCK2k.DRW
Intrinsic Safety Barrier
(Optional)
2 Wire
(shielded)
CAPACITANCE
LEVEL PROBE
220/115VAC
or
24VDC
4 SPDT RELAY
CONTACTS
Isolated 4-20mA
RS-485 Network
(2 Wire)
Isolated input
Probes upto 1km away