User manual
Model: 2100 &2300 Series
2100UM22.DOC Rev: 2.2
- 25 -
Press the SETUP key, then 3 for Settings and then 4 for mA Trim. The unit will put out what
it thinks is 20.0mA.
Disconnect any load connected to the mA output of the transmitter.
With an ACCURATE MULTIMETER MEASURE THE mA OUTPUT. The Multimeter should
have at least one place of decimal.
Enter this value at the prompt and press the Enter key. A maximum tolerance adjustment of
3% is allowed i.e. the entered value must be in the range of 19.4mA to 20.6mA. If a value out
of this range is entered an error is flashed on the screen. If this occurs, contact an Arjay
representative for assistance.
FILTER, ENGINEERING UNITS, TAG #:
These settings are described in Section 3.4.2, 3.4.3, and 3.4.4 respectively.