3.4.4 TAG NUMBER
THE TAG NO.s ARE USED ONLY FOR NETWORK APPLICATIONS AND ARE USUALLY
FACTORY SET. To communicate on a network, each controller must have a unique Tag Number
(also called node address).
Important: if multiple units on a network have the same address, network errors will result.
An Arjay Central Access Panel (CAP) is required to communicate with 2000 series level
controllers on a network. The CAP allows data to be viewed from and remote calibration / set of
any 2000 series level controller on the network from a central location.
Press the SETUP KEY if not already in the Setup menu, then press 3 for Settings, then 3 for
Tag #.
Enter the desired tag number.
3.4.5 mA SETTINGS
Press the CONTROL key:
**CONTROL SETTINGS**
1-Relay Settings
2-mA Settings
Press 2 to setup the mA output:
***SET mA OUT***
Zero (% Lvl) 0.0
Span (% Lvl) 100.0
Enter the level in percent for Zero and Span values followed by the Enter key in each case.
After the Enter key is pressed for the Span value, the following menu is displayed for
additional mA settings:
***SET mA OUT***
Action: Direct
Type: 4-20mA
Press 1 to change
The cursor will be on the Action setting line. Pressing 1 toggles between Direct and Inverse
action. Direct action causes the 4mA to be output when the level is at the Zero setting and
20mA to be output when the level is at the Span setting. Inverse action is the reverse of
Direct action. Press the ENTER key when done.
The cursor now drops to the Type setting line. Pressing 1 toggles between 4-20mA and 0-
20mA. The 0-20mA as the name implies, outputs a signal between 0-20mA instead of 4-
20mA. The 0-20mA setting generally offers a little better measurement resolution.
3.4.6 RELAY SETTINGS
For help in selecting the relay settings please refer to Sections 4.3.2 - 4.3.4.
Press the CONTROL key if not already in the Control Settings menu (see mA Settings
display above). The press 1 for Relay Settings:
** RELAY SETTINGS **
1-Relay1 2-Relay2