User manual

Model: 2100 &2300 Series
2100UM22.DOC Rev: 2.2
- 10 -
3.0 STARTUP AND CALIBRATION
This Section is provided for minimum setup. For a more detailed description of features please refer
to Section 4.0.
2300 SERIES MODELS: An Arjay Central Access Panel (CAP) or Handheld Calibrator is
required to access the “blind” 2300 series models. In either case, the keypad and LCD are as
shown in Figure 3.0.
Figure 3.0
3.1 NOTES ON VALUE ENTRY
When entering in numeric values, the cursor can be backspaced to correct mistakes by pressing the
DISPLAY key. This is only true if the cursor is not at the beginning of the displayed value, in which
case the DISPLAY menu is entered.
Values may be entered with any number of places of decimal.
If the entered value is out of the allowed limits, the system displays the limiting value for 2 seconds.
For example if the mA Span value is entered as 5000.0% then MAX. 100 are displayed for 2 seconds
then entry is allowed again. The current value is not changed unless the entered value is within
limits.
STATUS LED:
GRN = OK
RED = ERROR
RELAY LEDS:
ON = HI ACTING
ALARM
DISPLAY
CALIB
CONTROL
SETUP
DISPLAY KEY: Displays Level Information. Also used as backspace in value entry.
CALIBRATE KEY: For probe calibration menus.
CONTROL KEY: For 4-20mA output and Alarm Relay settings.
SETUP KEY: For configuration and diagnostics.