MODEL 2100 and 2300 SERIES CONTINUOUS LEVEL MONITORS User Manual Arjay Engineering Ltd. Oakville (Toronto), Canada, L6H 6C9 Tel . Fax. ++1 (905) 829-2418 ++1 (905) 829-4701 North America 1-800-387-9487 www.arjayeng.com arjay@arjayeng.
000 Series Level-Ease Monitor Continuous level monitoring of liquids and bulk solids Over 30 years of Arjay’s field proven HF capacitance technology has been applied to the Level-Ease 2000 monitors. This unique level system provides complete flexibility for one or more tank levels in one package.
2000 Series The Level-Ease 2000 sensing probe monitors the capacitance field between the probe and it’s concentric shield or the tank wall. As the level of product increases the probe capacitance changes. This level signal is used to provide outputs, displays, and relay control.
Model: 2100 &2300 Series 2100UM22.DOC Rev: 2.2 TABLE OF CONTENTS MANUAL DESCRIPTION ............................................................................................................ 3 FEATURE TABLE .......................................................................................................... 3 2300 SERIES CONTROLLERS ..................................................................................... 3 1.0 INSTRUMENT OVERVIEW........................................................
2100UM22.DOC Model: 2100 &2300 Series Rev: 2.2 MANUAL DESCRIPTION This manual describes the features, installation, setup, and usage of Arjay’s 2100 and 2300 series of Level Controllers. The 2100 series includes models 2110, 2112, and 2114. The 2300 series includes models 2310, 2312, and 2314.
2100UM22.DOC Model: 2100 &2300 Series 1.0 INSTRUMENT OVERVIEW 1.1 FEATURES 1.2 Rev: 2.
Model: 2100 &2300 Series 2100UM22.DOC Rev: 2.2 OPERATION The unit senses level using a RF Capacitance measurement technique for very high-resolution measurements. A probe mounted in a vessel forms a capacitor with the vessel wall (or with a concentric shield around the probe for non metallic vessels). The capacitance of this arrangement is directly proportional to the level of material in the tank and may be measured to provide signals and controls.
Model: 2100 &2300 Series 2.0 2100UM22.DOC Rev: 2.2 INSTALLATION NOTE: If any damage to the instrument is found, please notify an Arjay Engineering representative as soon as possible prior to installation. 2.1 PROBES Capacitance probes may be selected from a variety of styles for use with liquids, liquid interfaces, and granular materials. The probe length is customer specified for the height of material desired to be measured. Usually Teflon coated probes are used. 2.
Model: 2100 &2300 Series THREADED ENTRY 2100UM22.DOC Rev: 2.2 FLANGED ENTRY CONCENTRIC SHIELD ENTRY Use wrench on Lower Hex ONLY 2" Entry Typical 1- For threaded and flanged entry types, the probe must be parallel to the tank wall 2- For threaded and flanged entry types, measurement sensitivity is increased by reducing the probe to wall distance. 3- There should be good electrical conductivity between the tank wall and the transmitter enclosure.
Model: 2100 &2300 Series 2.3 2100UM22.DOC Rev: 2.2 MECHANICAL INSTALLATION MODEL 2100, 2300 SERIES LEVEL CONTROLLERS ENCLOSURE FRONT VIEW 4.65" 9.00" www.arjayeng.com Hole diameter 0.150" #6 bolt size (4 places typical) 1- Find a location on a vertical structure to mount unit about eye level in a protected area away from direct condensation. The structure should be able to support the weight of the unit. 2- Mount the unit via bolts into the vertical structure using the 4 mounting holes.
2100UM22.DOC Model: 2100 &2300 Series ELECTRICAL INSTALLATION All connections are via plug-in connectors for installation convenience. #2 + - #1 + - #2 + - #1 mA OUTPUTS Isolated mA sourced outputs - NOT loop powered! + - PROBE CONNECTION To PMC-2000 card in each Arjay level probe head. + + + - + + + 24VDC INPUT ( 500mA Internal Fuse) + - PROBES CAT I mA OUTS NET 24V Caution: to reduce the risk of fire or electric shock, do not interconnect the outputs of different terminals.
2100UM22.DOC Model: 2100 &2300 Series 3.0 Rev: 2.2 STARTUP AND CALIBRATION This Section is provided for minimum setup. For a more detailed description of features please refer to Section 4.0. 2300 SERIES MODELS: An Arjay Central Access Panel (CAP) or Handheld Calibrator is required to access the “blind” 2300 series models. In either case, the keypad and LCD are as shown in Figure 3.0.
Model: 2100 &2300 Series 2100UM22.DOC Rev: 2.2 During value entry, the capacitance and level are still being constantly updated in the background. Apart from the CALIBRATION menu and the DIAGNOSTICS menu, in all other menus, the Alarm relays and the mA output are also updated. 3.2 2300 SERIES USER INTERFACE Please skip this Section for 2100 series models which have an integral keypad and LCD. As described, the 2300 series models lack an LCD and keypad.
#2 #1 + - #2 + - + N/C + - #1 N/C + + - NET 24VDC mA OUTS The network connection is optional for the 2100 & 2200 series and standard on the 2300 & 2400 series models which require an Arjay Central Access Panel (CAP) or Handheld Calibrator for data access. Rev: 2.2 + + - PROBES All connections are via plug-in connectors for installation convenience. + - 2100UM22.DOC Model: 2100 &2300 Series + To PMC-2000 card in Arjay level probe head.
2100UM22.DOC Model: 2100 &2300 Series Rev: 2.2 After the startup screen, the LCD should show a screen similar to: LEVEL 10.00 in 13.88 % NOTE: The shown values are for example only. The 2nd line shows the vessel capacity in engineering units. One of 8 engineering units may be selected in the configuration menu as described in the next sub-section. The 3rd line shows the vessel capacity in percent. This value is independent of the engineering units.
2100UM22.DOC Model: 2100 &2300 Series Rev: 2.2 Current: gal Press the number for the desired units. 3.4.4 TAG NUMBER THE TAG NO.s ARE USED ONLY FOR NETWORK APPLICATIONS AND ARE USUALLY FACTORY SET. To communicate on a network, each controller must have a unique Tag Number (also called node address). Important: if multiple units on a network have the same address, network errors will result.
2100UM22.DOC Model: 2100 &2300 Series Rev: 2.2 3-Relay3 4-Relay4 5-Disable Alrms (ENA) Disable relays. Pressing 5 toggles between Enabling (ENA) and Disabling (DIS) alarms. The current state is displayed on the right extreme of the bottom line of the LCD. A Disable setting will disable Alarm relay alarms even if an Alarm condition exists. The factory default setting is ON (ENA) which allows Alarm relays activation. Relays can be enabled AFTER calibration and setup are complete.
Model: 2100 &2300 Series 2100UM22.DOC Rev: 2.2 above the High Setpoint. No action is taken when the process level is between the High and Low Setpoints. In the alarm condition, the corresponding alarm LED is turned ON, and the relay is energized. Low Yes Alarm condition set and reset as above. In the alarm condition, the corresponding alarm LED is turned ON, but the relay is de-energized. The Relay Settings menu is now displayed from which other relays may be selected to be set up.
Model: 2100 &2300 Series 3.4.8 2100UM22.DOC Rev: 2.2 FULL SCALE VALUE This is the maximum capacity of the vessel IN THE ENGINEERING UNITS CHOSEN IN Section 3.4.3. Press the CALIBRATION key to get to the CALIBRATION menu, then 4 for FS Value. The unit prompts for the maximum capacity of the vessel in the already chosen engineering units. Enter the vessel maximum value then press Enter. 3.4.
2100UM22.DOC Model: 2100 &2300 Series 4.0 Rev: 2.2 OPERATION IN THE FOLLOWING TEXT A MENU WILL BE DISPLAYED AS A PATH. FOR EXAMPLE THE AUTOCAL MENU: [CALIB\ 1]. (CALIB key then 1 for AUTOCAL). SETTINGS MENU: [SETUP\3] (SETUP key then 3 for SETTINGS). The 2000 Level Monitor uses a high precision and highly repeatable RF technique to measure capacitance, which in turn is used to calculate level.
00UM22.DOC Model: 2100 &2300 Series 4.2 CALIBRATION Rev: 2.2 [CALIB] The unit may be calibrated 3 different ways: Automatic Calibration and 2 Manual Calibrations. Pressing the CALIBRATION key enters the CALIBRATION menu: *** CALIBRATION **** 1-Auto 2-Manual 3-Slope/Off 4-FS val 4.2.1 AUTOMATIC CALIBRATION [CALIB\1] This is typically done for a new installation.
Model: 2100 &2300 Series 4.2.3 SLOPE AND OFFSET 2100UM22.DOC Rev: 2.2 [CALIB\3] Use this feature to view and or modify the SLOPE and OFFSET calibration values directly. Press the CALIBRATION key to enter the CALIBRATION menu then 3 for Slope/Off. Enter the desired SLOPE and OFFSET. If no change is desired just press the Enter key in each case or a Menu key to go to another menu such as the DISPLAY menu. 4.2.
2100UM22.DOC Model: 2100 &2300 Series Rev: 2.2 for the appropriate relay indicates the alarm condition. The relay is de-energized (with no delay) when the level falls below the low control point. Selecting low action will energize the relay when the level falls below the low control point for at least the time delay period. The relay is deenergized (with no delay) when the level rises above the high control point. 4. FAILSAFE.
Model: 2100 &2300 Series 2100UM22.DOC Rev: 2.2 Conditions 1, 3, 5, 7 are typically for control applications where the positive action i.e. turning on a pump, should be shut off during a power failure to the Arjay level controller. Conditions 2, 4, 6, 8 are typically for alarm applications where the positive action i.e. sounding an alarm if the level is at a high level, should also be in place during a power failure to the Arjay level controller. 4.3.
Model: 2100 &2300 Series 2100UM22.DOC Rev: 2.2 Since the pump should be turned off if the Arjay unit fails or in the event of a power failure i.e. the positive action state is not the same as the failure state, the failsafe setting should be No. Since the positive action is desired when the level drops below the low control point, the relay setting should be Low Acting. Since the pump starter requires power to turn on the pump, the normally open contacts should be used.
2100UM22.DOC Model: 2100 &2300 Series 4.4 SETUP MENU Rev: 2.2 [SETUP] The SETUP menu is used for one-time setup and for Diagnostics. ********SETUP******** 1-PMC 2000 2-Diags 3-Settings 4.4.1 PMC 2000 (Manual) [SETUP \ 1 \ 2] This menu is to calibrate the 2000 series controller for the particular PMC-2000 level transmitter module located at the probe head. There are 3 calibration parameters: A, K, C.
Model: 2100 &2300 Series 2100UM22.DOC Rev: 2.2 Press the SETUP key, then 3 for Settings and then 4 for mA Trim. The unit will put out what it thinks is 20.0mA. Disconnect any load connected to the mA output of the transmitter. With an ACCURATE MULTIMETER MEASURE THE mA OUTPUT. The Multimeter should have at least one place of decimal. Enter this value at the prompt and press the Enter key. A maximum tolerance adjustment of 3% is allowed i.e. the entered value must be in the range of 19.
Model: 2100 &2300 Series 5.0 2100UM22.DOC Rev: 2.2 TROUBLESHOOTING CONDITION DO THIS 1. DISPLAY MENU SHOWS: The unit is not receiving a frequency signal from the remote PMC-2000 level transmitter in the probe head: Check wiring. Error: No Xmtr Signal If wiring checks out: call Arjay Technical Support. An adjustment may be made at the controller. 2. DISPLAY MENU SHOWS: Error: Setup Values Bad This indicates that one of the calibration or setup parameters has been corrupted.
Model: 2100 &2300 Series 6.0 2100UM22.DOC Rev: 2.2 CONTROLLER SETTINGS SHEET Checked by Model Number Serial Number Software Rev. PARAMETER DESCRIPTION Probe A value Probe PMC-2000 level transmitter calibration value Probe K value Probe PMC-2000 level transmitter calibration value Probe C value Probe PMC-2000 level transmitter calibration value Slope Result of a successful Calibration: Capacitance change per % change. Used by unit to calculate the level in % and Eng.
Model: 2100 &2300 Series 2100UM22.DOC Rev: 2.2 set by Relay 1 Failsafe setting). Relay2 Hi Set Alarm Relay 2 High Setpoint: Alarm condition if level is above this value. 40.0% Relay2 Lo Set Alarm Relay 2 Low Setpoint: Alarm conditions cleared if level is below this value. 35.0% Relay2 Action Set for high or low acting (see Sections 4.3.2 – 4.3.4 for details) High Relay2 Failsafe Set for Failsafe or Non Failsafe Off Relay 2 Alarm Delay See Relay 1 Alarm Delay description.