Specifications

Type SSM Specication Guide
Low Voltage Products & Systems 13
ABB Inc. • 888-385-1221 • www.abb.com/lowvoltage 1SXU132173M0201 [AC 1007.2] - 2/02
D) Printed circuit boards shall be burned in for a minimum of 48 hours at 60°C.
E) The complete unit shall be functionally tested under load before shipment to assure proper operation per
specication. Complete test reports shall be available upon request.
7.0 Documentation
Final documentation will consist of the following:
A) Complete schematics and “as built” wiring diagrams
B) Enclosure elevations and layout drawings
C) System installation and startup manuals
D) All drawings shall be done in AutoCAD
8.0 Spare Parts
A recommended spare parts list, and associated pricing, will be supplied with each different solid state reduced voltage
starter when requested.
9.0 Field Acceptance, Testing and Training
A) Arrangements shall be made and costs included for on-site inspection and start up assistance to be performed
by a Factory Authorized Field Technician, prior to rst energization if required.
B) Provide minimum of 4 hours of eld training on site for operating and maintenance personnel, covering start
up, parameter changes, operations, trouble-shooting and repair techniques if required. Contact factory for
training costs. Adequate copies of job documentation and installation (Operation & Service manauals) shall be
provided.
C) Demonstration will include complete operating sequence, simulating eld controls if necessary, to the
satisfaction of the Engineer and/or Owner while the Field Technician is on site. Adjustments will be made as
necessary and a eld start up report will be provided upon conclusion.