Product specifications
Fixing the base to the wall
Using the five mounting holes provided (see figure 3 below), fix the base securely onto/into the wall. The
mounting holes are suitable for use with No.8-10, or 4-5mm countersunk screws.
A
ssess the condition and construction of the wall and use a suitable screw fixing.
Any dust or swarf created during the fixing process must be kept out of the fire alarm panel and care must
be taken not to damage any wiring or components.
Figure 3 : Internal view of the back box with PCBs removed / side view for flush mounting
CFP ALARMSENSE 2/4/8 ZONE INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002020 Rev 1 • Page 7 of 24
CFP ALARMSENSE 2/4/8 ZONE FIRE ALARM PANEL
AlarmSense™ zone circuit wiring
Depending on the model purchased, two, four or eight AlarmSense™ zone circuit connections are available
on the fire alarm panel. A maximum of 25 AlarmSense™ detectors or manual call points can fitted to each
circuit and these can be mixed in any order. AlarmSense™ sounders may also be included in this 25, however
there are limitations to the number of sounders which can be used (please refer to page 8 for important
advice on sounder loading and distribution).
Only AlarmSense™ devices can be used on the zone circuits.
Figure 4 : Typical zone circuit wiring
Connect an end-of-line (EOL) capacitor (provided in the panel ’s accessory pack) across the terminals of the
last device on each circuit to allow the wiring to be monitored. Zones that are not used must also have an
end-of-line capacitor fitted at the panel.
Note that an open circuit fault on zone wiring will stop some or all of the detectors, manual call points and
sounders operating, and a short circuit will stop all devices operating.
For more specific device wiring information, refer to the instructions provided with the AlarmSense™
devices used.
The wiring for each zone circuit should be connected to the relevant 5mm connector block on the Main
Control PCB and their screens terminated at the panel ’s base earth post (see page 13 for more precise
second fix connection details).
ALARMSENSE™
MANUAL CALL
POINT
+
PANEL ZONE
CIRCUIT
TERMINALS
–
+ +
ALARMSENSE™
OPTICAL/HEAT
DETECTOR
ALARMSENSE™
SOUNDER
ALARMSENSE™
MANUAL CALL
POINT
ALARMSENSE™
SOUNDER
ALARMSENSE™
OPTICAL/HEAT
DETECTOR
END OF LINE
CAPACITOR
DO NOT SPUR
(wiring not
monitored)
75mm
includes 'dimples'
WALL
339mm
170mm
Ensure no
fixing devices
are located
underneath the
Power Supply
P
CB to avoid
compromising
electrical
safety
Fixing centres
Fixing centres