Product specifications

CFP ALARMSENSE 2/4/8 ZONE INSTALLATION & MAINTENANCE MANUAL Approved Document No. DFU7002020 Rev 1 Page 11 of 24
CFP ALARMSENSE 2/4/8 ZONE FIRE ALARM PANEL
Figure 8 : Power Supply PCB layout and Mains connection details
Figure 9 : Battery location and connection details
DO NOT
ADJUST
BATTERY FUSE
1.6AF
+ Red
I Black
T
o
Battery
BAT1
PL2
A
UX 24V
PL1
T
o Main
Control
PCB
L
N
P
RIMARY
FUSE F1
1
ATH 250V HRC
L N
F
USE
CONN1
C
ONN1
Incoming Mains cable must be
segregated from other cables
and should only enter the panel
through either of these drill
outs. Good quality cable glands
must always be fitted.
PSU earth strap
Do not operate the
panel without this
strap connected.
Mains fuse (F1)
20 x 5mm 1A HRC
ceramic to IEC 127
(EN60127 Part 2).
Do not use any
other type or size of
fuse in this position.
Battery fuse (F2)
20 x 5mm 1A6 F to IEC
127 (EN60127 Part 2).
Do not use any other
type or size of fuse in
this position.
Battery leads
(supplied in the
panel’s accessory
pack). See below for
connection details.
L = Live; N = Neutral; = Earth.
The incoming Mains earth wire must be
connected to the terminal marked
and not to the base earth post.
(The PSU earth strap connects the PCB
to the base earth post.)
Hazardous Voltages Present light
When lit red, hazardous voltages will
be present on the components in the
shaded area of the PCB.
DO NOT TOUCH!
Certain components are charged to this
hazardous voltage during operation,
and this charge is bled away after the
Mains supply has been removed. When
the red light extinguishes, the charge
has leaked away to a safe level.
+
+
+
I
+
+
I
+
Location of small
sized batteries
typically 1.2 Ah
Location of medium
sized batteries
typically 2.1 Ah
+
+
+
Take care to arrange
batteries so terminals
do not touch
Location of large
sized batteries
typically 3.0 Ah
Connection of leads
to Power Supply PCB
Run the battery leads
(supplied) through slits
in the plastic ribs
R E D
BLACK
Nylon
tie wraps
Link wire