Two levels of control are available to user(s) of this fire alarm panel; General User and Authorised User.
1. General User Controls (access level one)
When the panel is in access level one, the indicator lights on the panel front give a comprehensive
overview of the system’s current status. Any fire and fault conditions are clearly displayed, disablements
highlighted and the status of all outputs reported. For detailed descriptions of what each indicator
means, see page 7.
The only functions that can be performed by the user when the panel is in access level one are:
Muting the panel’s internal sounder by pressing the Silence Internal Sounder button;
Overriding any delays (CFP model dependent - see page 3) which may have been programmed
into the panel by pressing the Silence/Activate Sounders button (only applicable when the panel
is in alarm); or
Putting the panel into access level two (the Authorised User state) - see below.
2. Authorised User Controls (access level two)
To avoid unauthorised changes to critical parts of the fire alarm system, controls such as silencing the
sounders, resetting an alarm condition and setting disablements are only accessible via a secure
method of entry which puts the panel into access level two.
To put the panel into access level two on the code entry version of the fire alarm panel:
Enter the code 2 1 4 3 using the code entry buttons on the panel front. During the code entry
sequence, the panel’s accessed light will pulse. If an incorrect sequence of numbers is entered after four
button presses the accessed light will stop pulsing and you must enter the code again. When the
correct code is entered, the accessed light will be lit steady to indicate that the controls are operative.
To exit access level two, press the Exit Access Mode button.
To put the panel into access level two on the keyswitch version of the fire alarm panel:
Turn the key to the I’ position (Note: The key cannot be removed when in this position). When the key
is in the I’ position, the accessed light will be lit steady to indicate that the controls are operative.
To exit access level two, turn the key back to the O’ position.
Details of how to use the Authorised User controls can be found on pages 8 to 11 of this user manual.
CFP USER MANUAL Approved Document No. DFU7001010 Rev 1 Page 6 of 20
CFP 2/4/8 ZONE CONVENTIONAL FIRE ALARM PANEL
1 2 3 4 5 6 7 8
supply
p
resent
remote
o
utput test accessed
general
d
isablement
fault
o
utput
status
remote
o
utput
status
general
f
ault
s
ystem
f
ault
r
epeater
f
ault
s
ounder
s
tatus
o
utput
d
elays
Zone fault/disabled/test
1 2 3 4 5 6 7 8
Fire Zones
1
2
3
4
5
6
7
8
S
ilence/Activate
sounders
Control Panel
Reset
Next
option
Enable/
D
isable
S
ilence Internal
sounder
power
s
upply
fault
auxiliary
o
utput
status
Lamp
test
I
O
Code
e
ntry
1
2
3
4
E
xit Access
M
ode
The keyswitch panel
version DOES NOT have
the push buttons shown
in this hashed area.
The code entry panel
version DOES NOT have
the keyswitch shown in
this hashed area.
PANEL LAYOUT/ACCESSING THE CONTROLS
The fire alarm panel is available in two front panel versions; keyswitch and code entry (CFP model dependent - see
page 3), allowing different methods for entering access level two. Note: Repeater Fault and Output Delays lights
are not on the CFP Economy Panel.