Specifications

9
Series RMB Hot Runner Controller Instruction Manual
3.1 Setting Switches
The factory switch settings are shown
below.
Location of DIP Switches
SW2-switch 1 – OFF for soft start only
when ground fault has been detected;
ON (default) for soft start every time
controller is powered up.
SW2-switch 2 – OFF (default) for J
thermocouple input; ON for K
thermocouple.
SW2-switch 3 – OFF for degrees
Fahrenheit; ON for degrees Celsius.
Default depends on shipping destination:
OFF for North America
ON for all other destinations.
SW2-switch 5 – OFF (default) for normal
operation; ON to load default parameter
values the next time controller is powered
up.
SW2-switch 8 – OFF – Normal
ON – Loop Break Disabled
SW2-switch 4 is used only at the factory.
SW2-switches 6, 7, and 8 are not used.
Leave them off.