Specifications
4
Series RMB Hot Runner Controller Instruction Manual
1.3 Specifications
1.3.1 Operating Limits
Ambient Temperature 32°F to 131°F (0°C to 55°C)
Relative Humidity Tolerance 10 to 95% Non-Condensing
Shipping Temperature –40°F to 158°F (–40°C to 70°C)
Power Requirements 115 to 240 Vac 50 or 60 Hz nominal, CE compliant
1.3.2 Performance
Accuracy ± 0.3% of span
Setpoint Resolution 1 degree Fahrenheit
Repeatability ± 0.1% of span
Temperature Stability ± 0.5% of full scale over the ambient range of 32°F to
131°F (0°C to 55°C)
Thermocouple Cold-End Tracking automatic, better than 0.02°F per °F
(0.01°C per °C)
Noise Rejection Common Mode > 100 dB, Series Mode > 70 dB
Process Sampling Rate 10 Hz (100 ms)
1.3.3 Connections and Mounting
The Series RMB controllers are designed for installation in a Hot Runner
mainframe (or other compatible mainframe). Removal of an RMB controller
from the mainframe requires removal of a locking pin (standard controllers) or
locking screw (CE-compliant controllers).
1.3.4 Inputs
Thermocouple J or K
Supported Sensor Range 32 to 999°F (0 to 537°C)
1.3.5 Output
TRIAC, 15 amps at 120/240 Vac (30 amp optional), driven by optically isolated
interface circuit. Protected with a pair of 15 amp (or one 30 amp) field-
replaceable fuses. Instructions for replacing the fuses are in 6.3. Replacement
fuses must be Type F fast-acting 250 Vac fuses rated at 15 amps (or 30 amps).
A 15 amp (120/240 Vac) relay (30 amp optional) interrupts power to the heater if
the controller detects shorting of the TRIAC output or other system failures.
A ground fault detection circuit is also standard.