Installation manual

031-171-C0-003 Rev. C 33
2 19" Swing-Away
equipment rack
1 Securing Bolt
1 Securing Bolt
3 Enclosure
Ground Bar
Fig. 3-5, 19” Swing Rack (RMB-E-911-C)
3.0 Installation, cont.
3.5 19” Swing Rack and Equipment Installation
The 19” swing rack can swing 90° to the left to allow access to the cables and rack-mounted
equipment. It is grounded to the enclosure.
1 To swing the rack, loosen the captive securing bolts at the top and bottom right corners and swing
the rack to the left.
2 When installing equipment in the rack, provide a long enough service loop to prevent damage to
cables when swinging the rack open.
Allow at least a 1” ventilation space between installed rack mount units to allow for air flow in the
enclosure.
3 Rack-mounted equipment should be grounded to the enclosure ground bar at the rear of the
enclosure.