Installation manual
031-171-C0-003 Rev. C 31
50°F/10°C
59°F/15°C
68°F/20°C
77°F/25°C
86°F/30°C
95°F/35°C
104°F/40°C
40° C Maximum Internal Temp.
38° C Startup
34° C Shutdown
38° C Setpoint
33° C Startup
29° C Shutdown
33° C Setpoint
28° C Startup
24° C Shutdown
28° C Setpoint
23° C Startup
19° C Shutdown
23° C Setpoint
18° C Startup
14° C Shutdown
18° C Setpoint
Temperature Setpoint Jumper
System Setpoint Jumper
This jumper determines what temperature the
system will maintain inside the enclosure. The
diagram details the start and shutdown
temperatures for each setting. For default jumper
settings, see Fig. 3-4, Air Conditioning Wiring
Diagram.
Remote Temperature Sensor Jumper
This jumper determines where the control card gets its temperature information. In the LOCAL position
the card receives temperature information from it’s onboard temperature sensor. In the RMT position,
temperature information is received from an optional Remote Temperature Sensor that can be placed
anywhere in the enclosure. For default jumper settings, see Fig. 3-4, Air Conditioning Wiring Diagram.
Major and Minor Alarm Jumpers
This jumper determines the state of the alarm relays in the non-alarm state. In the NO position, the
non-alarm state is OPEN. In the NC position, the non-alarm state is CLOSED. For default jumper
settings, see Fig. 3-4, Air Conditioning Wiring Diagram.
3.0 Installation, cont.
3.3.4 Air Conditioner Control Card Jumper Settings