Instruction manual

ORDER# MODEL# SETTING OPTIONS DEFAULT
RMDC Units Without FAI Capability
03015 RMDC-1248F V1 (Down) Serves no function Zones 1-8: V2 (Up)
V2 (Up) Selects voltage from power supply unit 1*
03017 RMDC-1248 V1 (Down) Serves no function Zones 1-8: V2 (Up)
V2 (Up) Selects voltage from power supply unit 1*
03014 RMDC-12416F V1 (Down) Selects voltage from power supply unit 1* Zones 1-8: V2 (Up)
V2 (Up) Selects voltage from power supply unit 2* Zones 9-16: V1 (Down)
03016 RMDC-12416 V1 (Down) Selects voltage from power supply unit 1* Zones 1-8: V2 (Up)
V2 (Up) Selects voltage from power supply unit 2* Zones 9-16: V1 (Down)
RMDC Units With FAI Capability
03021 RMDC-PS5-M-8-UL-FAI V1 (Down) Constant voltage output Zones 1-8: V2 (Up)
V2 (Up) FAI Controlled Output
03022 RMDC-PS5-M-8F-UL-FAI V1 (Down) Constant voltage output Zones 1-8: V2 (Up)
V2 (Up) FAI Controlled Output
03024 RMDC-PS5-MD-16-UL-FAI V1 (Down) Constant voltage output Zones 1-16: V2 (Up)
V2 (Up) FAI Controlled Output
03025 RMDC-PS5-MD-16F-UL-FAI V1 (Down) Constant voltage output Zones 1-16: V2 (Up)
V2 (Up) FAI Controlled Output
* As identified on labels on the back of the unit.
AlarmSaf, Inc. 65A Industrial Way, Wilmington, MA 01887 978-658-6717 www.alarmsaf.com
8
RMDC Series Installation Instructions 52-376 Rev B01
J3
J4
J6
J7
REFER TO NAMEPLATE LABEL
FOR INSTALLATION DOCUMENT
REFERENCE NUMBER
J1 J2
J5
J8
SPARE
3
CAUTION:
FOR CONTINUED PROTECTION AGAINST RISK OF FIRE
REPLACE FUSES ONLY WITH SAME TYPE 3A 32V FUSE
DISCONNECT AC CORD BEFORE CHANGING FUSE
ATTEN
TION:
UTILISER UN FUSIBLE DE RECHARGE
DE MEME TYPE 3A 32V
DE’BRANCHER AVANT DEREMPLACER LE FUSIBLE
ZONES 1 - 8 ZONES 9 - 16
D1 D2 D3 D4 D5
D6 D7 D8 D9 D10 D11 D12 D13 D14 D15 D16
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
F1 F2 F3 F4 F5 F6 F7 F8 F9 F10 F11 F12 F13 F14 F15 F16
JP1 JP2 JP3 JP4 JP5 JP6 JP7 JP8 JP9 JP10 JP11 JP12 JP13 JP14 JP15 JP16
V1
V2
V1
V2
3.1.3 Front Panel Jumpers (Optional)
Not all RMDC models have front panel jumpers. When present, these
jumpers correspond to individual outputs and allow the selection of
certain settings or functions depending on the model. RMDC units
with front panel jumpers are listed below with settings. Models not
listed do not have front panel jumpers
Front panel jumpers must be set before initial
power-up. Do not change jumper settings while the unit is
powered or damage to the system can occur.