Instruction manual

SECTION I: ELECTRICAL RATINGS & SPECIFICATIONS
Electrical Ratings
SINGLE SUPPLY DUAL SUPPLY
PTC Output Fuse Output PTC Output Fuse Output
Input Voltage 120VAC 50-60Hz
Input Power 170 Watts Maximum 340 Watts Maximum
Max Total Output 8A @ 12V, 4A @ 24V 8A @ 12V, 4A @ 24V - Per Supply
Max Individual Output 1.6A/Output 3A/Output 1.6A/Output 3A/Output
Efficiency
˜
85%
Ripple <0.25% Typical, <0.50% During Battery Charge
Input Frequency 50-60Hz
Min Bat Charge Capacity 7Ah Per PS5-M Power Supply
Max Bat Charge Capacity 80Ah (48 Hour Charge) Per PS5-M Power Supply
Max Bat Charge Current 2A Per PS5-M Power Supply
Max Bat Standby Current 80mA Plus Total Output Load Per PS5-M Power Supply
Power Supply Module
AC CONNECT
EARTH GRND
DETECT
BAT
DETECT
VOLTAGE
SELECT
AC ON
EARTH HOT NEUTRAL
J1
WHT
BLK
GRN/YEL
JP3
120VAC Jumper
JP4 ABC
COM
FLT
AC
FLT
GRND
FLT
DC
OK
NO NC C NO NC C
AC FLT COM FLT
15
BATTERY
FUSE
BAT+ BAT– DC+ DC–
ACCESSORY MODULE
MOUNTING AREA
MODEL PS5–M
REPLACE FUSES ONLY WITH
SAME STYLE AND RATING
FUSE RATING: ATM 15A
CP1
CP2
12V
24V
POWER INPUT
120VAC: 150W
240VAC: 114W
AC SELECT JUMPER
FACTORY SET FOR 120VAC
EARTH GROUND
OPTION JUMPER
BATTERY PRESENCE
OPTION JUMPER
VOLTAGE SELECT
SWITCH
COMMON FAULT
VISUAL INDICATOR
AC FAULT
VISUAL INDICATOR
GROUND FAULT
VISUAL INDICATOR
BUSS OUTPUT
CONFIGURATION
JUMPER
ABC ACCESSORY
CONNECTOR
COMMON FAULT
RELAY CONTACTS
BATTERY FUSE
ATM-15A
BATTERY CONNECT
OBSERVE POLARITY
DC OUTPUT
OBSERVE POLARITY
DC OUTPUT
VISUAL INDICATOR
AC FAULT
RELAY CONTACTS
AlarmSaf, Inc. 65A Industrial Way, Wilmington, MA 01887 978-658-6717 www.alarmsaf.com
4
RMDC Series Installation Instructions 52-376 Rev B01
Temperature Specifications
Ambient temperature range: 0ºC to 49ºC (32ºF to 120ºF)
Ambient humidity: 93% @ 32ºC (90ºF) maximum
BTU output: 85 BTU/hr max (single) 160BTU/hr max (dual)
Mechanical Specifications
Weight: Approx. 14 lbs. (model dependent)
Overall size: 19.00”W x 10.75”D x 3.50”H (depth includes terminal
strips on back panel