Specifications
Doors
TM
Users Guide Keri Systems, Inc.
8-10 Section 8: Multiple Sites 01914-008 Rev. 5.3
3.7 Site Global Secure Time
The global secure time field allows an operator to enter a time-of-day when all non-time zone controlled
doors in the access control network should be locked. This ensures that regardless of the door status
during the day, all non-time zone controlled doors in the access control network are locked at least once
a day. The default value for this field is 17:30 (5:30 P.M.).
NOTE: Doors that have an Unlock/Lock Time Zone value of Never are not under automatic time zone
control and are eligible to be locked by the global secure time feature.
NOTE: All times are set to a 24-hour clock. For example, 5:30 P.M. is 17:30 under a 24-hour clock.
1. Click on the “Global Secure Time” cell for the site.
2. Type the global secure time for the site. For example, the global secure time for the parts
warehouse should be 22:30 hours (10:30 P.M.); type 22:30 (see Figure 8-10 on page 11 of this
section).
3.8 Site Global Unlock Enable
The global unlock enable button allows an operator to program the general purpose input on the master
controller such that an active signal on the input immediately unlocks all doors on the access control
network (refer to the PXL-250 Tiger Controller and SB-293 Technical Reference Manual
- P/N 01836-
003 or the PXL-250 Quick Start Guide
- P/N 01835-002 for general purpose information). The general
purpose input is a normally-open input. To activate this input, the input terminals must be closed
(shorted together).
NOTE: The global unlock enable feature is not fire marshall approved. Check your local codes for
fire safety management.
1. To enable the global unlock input, click on the button. The button toggles to
(see Figure 8-10 on page 11 of this section).
2. To disable the global unlock input, click on the button. The button toggles to
(see Figure 8-10 on page 11 of this section).