4.2 Link Configuration
The Link Config tab allows an operator to customize the controller’s output responses to events at the
controller’s inputs (see Figure 6-37). Input points can be linked to output points, allowing a change of
state at an input to activate an output relay. Blank input and output point name fields indicate those
inputs and outputs are reserved by the controller for door control and are not available for link
assignment. The following rules apply for link configuration.
• Up to 32 links can be defined per controller.
• Any input can be used by all 32 links.
• Inputs on a controller can only be linked to outputs on the same controller.
• Multiple inputs can be linked to multiple outputs using OR/AND functions allowing an operator to
create complex input/output links.
• Outputs on one controller can be hard-wired to inputs on other controllers.
Figure 6-37: Link Configuration Window
4.2.1 Link Parameters
The following list is the parameters that need to be configured when defining an I/O link. Refer to
Figure 6-37 to locate the parameter fields. Following this list is an example of an I/O Link.
Controller
The Controller field allows the operator to select the controller with I/O links to be configured.
1. Click on the arrow in the “Controller” field and a list of the controllers with available I/O points
appears.
2. Scroll through this list and click on the controller which has the I/O points to be configured.