Specifications
Keri Systems, Inc. Doors
TM
Users Guide
01914-003 Rev. 5.4 Section 3: Database Programming 3-39
4.2.10.2 PXL with a Satellite Board (SB) Configured in 2-Door Mode
Satellite Boards add output relays that can be dedicated to separate annunciation of door forced and
door held alarms. When a Satellite board is configured for 2-door operation, two of the board’s four
relays are automatically configured for the second door lock and alarm output annunciation. The
remaining two relays are eligible to be dedicated to the other alarm annunciation functions, allowing
door forced alarms to be separated from door held alarms for both doors.
NOTE: To have separate annunciation of door forced and door held alarms, the output relay points
must have been dedicated to alarm annunciation. This process is described in “Configure Dedicated I/
O Points” on page 17 in section 3.
Table 1 summarizes the options available to a PXL with a Satellite Board configured for 2-door
operation.
For example, A-Door and B-Door are configured in 2-Door mode.
• The A-Door needs to be monitored for just the door forced condition.
• The B-Door needs to be monitored for both door forced and door held open conditions on separate
alarm outputs.
A-Door
1. To set the door forced and door held alarm output values, click on the Setup ⇒ System pull-down
menu or click on the tool bar button. Then click on the Doors tab. If the “Door Forced
Output” and “Door Held Output” columns do not appear in the window, use the scroll bar at the
bottom of the window and scroll to the right until these columns appear.
2. To set the A-Door alarm output, scan down the door name column and locate the door to have
alarm output values assigned.
3. Locate the “Door Forced Output” column and click on the cell corresponding to the selected door.
Table 1: Alarm Annunciation Options PXL/Satellite Board
Door Forced Door Held Comment
A-Door
Disabled Disabled no alarm
annunciation
Alarm Out relay on
PXL
Alarm Out relay on
PXL
Door Held alarm is
annunciated with Door
Forced alarm
GP 4 Output on SB
(dedicated output
point)
Door Held alarm is
annunciated at its own
alarm relay
B-Door
Disabled Disabled no alarm
annunciation
GP 2 Output on SB
(default Alarm Out
relay)
GP 2 Output on SB
(default Alarm Out
relay)
Door Held alarm is
annunciated with Door
Forced alarm
GP 3 Output on SB
(dedicated output
point)
Door Held alarm is
annunciated at its own
alarm relay