Specifications
PN# 500-10420
Page 12 Rev. F, 02/11
Appendix B
Wire Gauge Factoring
1.1 Remote Power Supply
The Magnalock requires adequate voltage and current for proper operation.
Resistance is created by the length and gauge (size) of the wire being used.
An accurate estimated distance from the power supply to the opening is crucial.
For superior operation the correct size gauge wire must be used.
The devices used operate the best with the least amount of resistance on the source.
Using the correct gauge wires protects against large voltage and current (load) losses.
The gauge is determined by the wire distance, voltage and current of all devices.
1.2 Determining Wire Gauge
Follow Example A (12VDC system) and Example B (24VDC system) below.
Use Tables 1 and Table 2 to choose the correct wire gauge for the application.
1.2.1 Example A: (12VDC system)
Devices Used Amps (12VDC) Progressive Totals
M62 Magnalock 0.250 0.250
DK-26 Access 0.160 0.410
XMS Motion 0.050 0.460
EEB2 Timer 0.025 0.485
Total Current Rounded Up (Table 1)
0.600A
Using Table 1 (12VDC) Find: - Current Draw .600 Amps
- Wire Distance 200 Feet (One-Way)
Solution: 18 Gauge is indicated for proper installation
1.2.2 Example B: (24VDC system)
Using Table 2 (24VDC) Find: - Current Draw .400 Amps
- Wire Distance 1000 Feet (One-Way)
Solution: 14 Gauge is indicated for proper installation
Devices Used 24VDC Amps Progressive Totals
M82 Magnalock 0.200 0.200
TSB Touch Bar 0.025 0.225
DK-11 Access 0.070 0.295
XDT-24 Delay 0.050 0.345
MK Bypass/Reset 0.020 0.365
Total Current Rounded Up (Table 2)
0.400A