MECHANICAL RATINGS
Static Strength
Dynamic Strength
Endurance
1500 lbs - force
70 ft - lbs - force
250 000 cycles
MINIMUM WIRE GAUGE
REQUIREMENTS
Solenoid Voltage
24 VDC 12 VDC
200 feet or less 18 gauge 14 gauge
200 - 300 feet 18 gauge 12 gauge
300 - 400 feet 16 gauge 12 gauge
This electric strike is equipped with a field selectable 12 V DC/AC and 24 V DC/AC dual voltage solenoid.
12V is preselected.
CAUTION!
Before connecting any device at the installation site, verify input voltage and current using a multimeter.
Many power supplies and transformers operate at higher levels than listed. Any input voltage exeeding 10% of solenoid
rating may cause severe damage to the unit and will void the warranty.
GENERAL INFORMATION
Alarm Controls electric strikes are not polarity sensitive.
1 2
12 V/0.2 A
24 V/0.1 A
DC/AC
1 2 3 4 5
24 V 12 V
Strike
solenoid
WIRING AND VOLTAGE SELECTION
FAIL SAFE/FAIL SECURE SELECTION
ELECTRICAL RATINGS Continuous Duty
FOR SOLENOID
12 VDC 24 VDC 12 VAC 24 VAC
Resistance in Ohms 58 230
Watts Seated 2.5 2.64 1.56 1.68
Amps Seated .21 .1
1
.13 .07
AES-100 (fail secure)
Solenoids are rated at +/- 1 0% indic ated value
SPECIFICATIONS
58 230
Limited Lifetime Limited Warranty
WIRING DIAGRAMS AND GENERAL SPECIFICATIONS
-10°C to +40°C, 14°F to +104°F
Operating Temperature
Fail secure
Dual Voltage
12/24V AC/DC
Fail safe