5.1.4 PARAMETERS’ ADJUSTMENT
Authorized service can change seven of the parameters related to boiler
operation via using the reset button and knobs on the control board.
1) Ignition Gas Pressure: It controls the outlet gas pressure of gas valve
during ignition period. By using Table 6, adjustment can be done as
percentage.DefaultsettingofP01ignitioncapacityis16%.Incase
of a bursting type of burning, this parameter can be adjusted to meet
sufficient ignition capacity for a proper burning.
2) Gas Type: It makes the adaptation of the electronic board to gas type
change.
3) OFF Time: It is the time between boiler stop and restart again fol-
lowing the heat requirement. The boiler will not restart before this
time. Factory setting is 60 seconds. It can be altered between 0-255
seconds’ period as percentage by using Table 6.
4) Maximum Heat Capacity: It controls the heat capacity by controlling
thegasowpassingthroughthegasvalve.Defaultsettingis100%.
Itcanbeadjustedbetween0–100%.
5) Central Heating Range: The boiler can work in two different modes
using this parameter. There are two choices ‘ON’ and ‘OFF’. Default
setting is ‘OFF: 30-85°C’. The mode ‘ON: 30-50°C’ is recommended
foroorheatingsystems.
6) Domestic Hot Water Switch Off Temperature: It adjusts the switching
point of domestic hot water. There are two choices ‘ON’ and ‘OFF’.
Factory setting is ‘ON: boiler turns off at 71°C and starts at 70°C’.
With the other mode ‘OFF’ the boiler can be adjusted to ‘turn off at
“set + 8 °C” and start at “set + 7 °C”’.
ATTENTION! These adjustments should be done by authorized Alarko
Carrier Services.
5.1.4.1 Parameters Menu Activation
• InordertoenterparametermenuactivationDHWknobmustbeout-
side OFF range.
• Enteringparametermenuanyrunningrequestisrespected.