Technical data
53
For G20 20 mbar
For G30 29 mbar
For G31 37 mbar
For a mixed G30 and G31 29 mbar
6) Start and run the boiler to inspect any abnormal situation.
* When LCD backlight is ON, LED strip is switched OFF independently
fromLEDstripcongurationvalue.
Parameter P01; It controls the outlet gas pressure of gas valve during
ignitionperiod.DefaultsettingofP01ignitioncapacityis16%.
Parameter P02; This parameter is used to identify the type of gas that
is used. The default value of this parameter is adjusted for natural gas
(00).
5. OPERATING PARAMETERS
HARMONY_D USERS INSTALLATION AND SERVICE MANUAL
42
5. OPERATING PARAMETERS
Table 5 Setting the Parameters
Parameter
No
Description Default Notes
P01
Ignition capacity percentage;
can be modulated between 0-63%
16 %
P02 Gas Type 00-NG
00-NG
01-LPG
P03
CH off time;
60
Sec
P04
Maximum CH capacity
100
%
P05 Range CH 00
00-Normal
01-Reduced
P06 DHW switch off temperature 01
00- 65 °C
01- ON (Set point)
P07 LED strip configuration 01
00- LED always ON*
01-LED ON when flame is ON
02- LED always OFF
* When LCD backlight is ON, LED strip is switched OFF independently from LED strip
configuration value.
Parameter P01; It controls the outlet gas pressure of gas valve during ignition period.
Default setting of P01 ignition capacity is 16 %.
Parameter P02; This parameter is used to identify the type of gas that is used. The default
value of this parameter is adjusted for natural gas (00).
Parameter P03; It is used to identify the burner switch ON delay in CH mode. During a CH
demand, burner is switched OFF when T flow sensor is greater than T set + 5 ºC while pump
is running. When T flow sensor is lower than T set -3 ºC, burner is switched ON after the
delay fixed by the parameter P03.
Parameter P04; While adjusting P4 parameter, burner power follows trimmer P5 changes.
Parameter P05; If parameter 5 is OFF (00), CH range is normal (30ºC-80ºC), if it is ON
(01), CH range is reduced (30ºC- 50ºC), which is suitable for floor heating applications.
Parameter P06; If parameter 6 is ON, burner is switched ON and OFF according to set point.
If parameter 6 is OFF, burner is switched ON and OFF according to a fixed set point.
Parameter P07; If P07 is selected to be 00, the LED illumination is always ON. If this
parameter is 01 than, the LED lights will be ON when there is flame and if this parameter is
02, LED is always off.
5.1 Programming operating parameters
5.1.1 Parameter menu activation
In order to enter parameter menu activation, DHW knob must be outside the OFF range.
Entering parameter menu any running request is respected.
By pressing the RESET switch for more than 10 sec. P01* appears on the LCD display.