Technical data

26
5) The advice and instructions given in this document covers, as far
as possible, the foreseeable situations, which may arise. Contact
manufacturer for further advice if required.
6) Installationusingthestandarduekitisdescribedinthemaintextof
these instructions. NO OTHER FLUE KITS OR EXTENSIONS MAY
BE USED WITH THIS APPLIANCE
7) These appliances are for use with SEALED SYSTEMS ONLY.
4.1.2 BOILER LOCATION
1) This appliance may be installed in any room provided that attention
is drawn to the requirements of the relevant national and local rules,
standards and regulations in force in the countries of destination.
Where it is installed in a room containing a bath or shower, any elec-
trical switch or appliance control using mains electricity must not be
able to be touched by a person using the bath or shower.
2) The appliance is not suitable for external installation.
3) The appliance does not require any special wall protection.
4) The wall must be capable of supporting the weight of the appliance.
(See Table 1.)
5) Always consider the possible need to disconnect the pipes from the
appliance after installation.
6) The following clearances on Table 2 must be available for installa-
tion and for servicing.
HARMONY_D USERS INSTALLATION AND SERVICE MANUAL
18
6) Installation using the standard flue kit is described in the main text of these instructions.
NO OTHER FLUE KITS OR EXTENSIONS MAY BE USED WITH THIS
APPLIANCE
7) These appliances are for use with SEALED SYSTEMS ONLY.
4.1.2 BOILER LOCATION
1) This appliance may be installed in any room provided that attention is drawn to the
requirements of the relevant national and local rules, standards and regulations in force in
the countries of destination. Where it is installed in a room containing a bath or shower,
any electrical switch or appliance control using mains electricity must not be able to be
touched by a person using the bath or shower.
2) The appliance is not suitable for external installation.
3) The appliance does not require any special wall protection.
4) The wall must be capable of supporting the weight of the appliance. (See Table 1.)
5) Always consider the possible need to disconnect the pipes from the appliance after
installation.
6) The following clearances on Table 2 must be available for installation and for servicing.
Table 2 Clearances for boiler installation
Clearances
Above the casing
200 mm
Below
100 mm
Right hand side
30 mm
Left hand side
30 mm
7) If the boiler is to be installed in a timber framed building it should be fitted in accordance
with the relevant National and local rules and regulations in force, if any.
8) No combustible surface must be within 75 mm of the casing. If there is need to adjust near
a combustible surface, follow the clearances on Table 2.
9) The appliance can be installed in a cupboard used for airing clothes provided that the
requirements of relevant National and local rules and regulations (if any) are maintained.
7) If the boiler is to be installed in a timber framed building it
shouldbettedinaccordancewiththerelevantNationaland
local rules and regulations in force, if any.