Specifications
19
A
B
W W W
They can be changed according to local standarts.
Note : These dimensions are recomendations only.
H : Height of the boiler room must be minimum 1000 mm
heigher then the boiler height.
A : Burner lenght.
W : A + 200 mm minimum.
B : 600 mm minimum.
L : Lenght of boiler.
D : L/2 + 500 (min 600 mm)
L
L+600
500
A
BOILER ROOM LAYOUT
D