Specifications
- 14 -
Before firing the burner, be sure that system is full of water and all control items are
set to desired value and working properly.
Check the fuel pressure, temperature and fuel line leakages before running the
burner.
Run the burner and adjust it to proper output according to boiler needs.
Analyze the flue gas and be sure that emission levels of CO, NO
x
, soot, CO
2
or O
2
are according to current regulations.
For reference (current and local regulations has priority)
FUEL
% C0
2
CO (mg/kWh)
NO
x
(mg/kWh)
Gas
≥ 10
≤ 100
≤ 170
LPG
≥ 10
≤100
≤ 230
Oil
≥ 13
≤110
≤ 250
Note: Emission values shall be according to current and local limitations. In absence of
local limitations refer to current EN 677 for gas firing and current EN 300-2 for oil firing.
In correct adjustments can cause damage to people, animals, nature and also loss of
energy.
After running the burner heat the system up to 85 °C and again bleed the air in the
water side. After first heating most of the dissolved air in the system water will be free
for bleeding.
Control all the security and operation devices for proper operation and set values are
according to system needs again.
Call the owner or operator of the boiler house and give the necessary information for
proper operation of the system and warn them about the possible dangers and
limitations and what will they do in case of emergency.